Instrument Transformer Insulation Paper: Grades, Specs & Sourcing Guide

Instrument Transformer Insulation Paper: Grades, Specs & Sourcing Guide

TL;DR — Instrument transformer insulation paper in 30 seconds:

  • Oil-immersed instrument transformers (CTs and VTs) use cable paper, capacitor tissue, and crepe paper — the same cellulose family as power transformers, but with tighter requirements on dielectric loss (tan δ), thickness uniformity, and cleanliness.
  • High-voltage cable paper (0.08–0.17 mm) covers main insulation; capacitor tissue serves CT interlayer and condenser grading structures; crepe paper wraps leads and bends.
  • Governing material standard: IEC 60554 (cellulose papers); product-side requirements come from the IEC 61869 instrument transformer series.
  • Buy on batch test reports: tan δ, dielectric strength, thickness tolerance, moisture, and conductivity — not on a generic datasheet.

Instrument Transformer Insulation Paper: Grades, Specs & Sourcing (Quick Answer)

Instrument transformer insulation paper is electrical-grade cellulose paper — high-voltage cable paper, capacitor tissue, or crepe paper per IEC 60554 — selected for oil-immersed current and voltage transformers where low dielectric loss (tan δ), tight thickness tolerance, and high purity directly determine measurement accuracy and partial discharge performance. Unlike power transformer paper, which is specified mainly for dielectric and mechanical strength, instrument transformer paper must also keep dielectric losses low enough that the CT/VT neither heats nor drifts in accuracy over a 30-year metering life. This guide maps the paper grades to each position inside a CT/VT, gives the specification table to write into an RFQ, and covers the acceptance tests that matter.

Why Instrument Transformers Are a Special Case

A current or voltage transformer is a measuring instrument first and a power device second. That changes what insulation paper must do:

  • Dielectric loss is a metering problem, not just an aging problem. In a power transformer, tan δ mostly predicts heating and aging. In a CT/VT, dielectric loss in the insulation system also shows up as phase error — directly degrading accuracy class. Paper with low, stable tan δ is a measurement component.
  • Partial discharge limits are tighter. PD does not just erode insulation; it can mask or mimic real grid signals and corrupt measurement. Paper cleanliness (no metallic inclusions, no fiber bundles) and uniform impregnation are specification items, not marketing adjectives.
  • Small oil volume, high field stress. Instrument transformers pack high voltage into compact oil volumes. There is little thermal mass and little margin — paper defects that a large power transformer might tolerate become accuracy or failure events in a CT.
  • Long calibration life. Metering CTs are expected to hold accuracy class for decades; the insulation system must age predictably and slowly.

Paper Grades and Where Each One Goes

Paper Grades and Where Each One Goes

Position in CT/VT Paper grade Key requirements
Main insulation (core/coil wrapping) High-voltage cable paper, 0.08–0.17 mm Low tan δ, high dielectric strength in oil, uniform thickness
Interlayer / condenser grading insulation Capacitor tissue / thin cable paper Very tight thickness tolerance, high density, low conductivity
Lead and tap wrapping Crepe paper, crepe paper tape 50–100% elongation, conformability without cracking
Shield/end-region wrapping Crepe paper or semi-conductive crepe Field grading compatibility
Spacers, end rings, structural parts Pressboard (IEC 60641-2) Density grade, mechanical stability

High-voltage cable paper (common grades in 0.08, 0.12/0.13, and 0.17 mm) is the workhorse: it wraps the wound core-coil assembly and builds the main insulation. For 110–330kV instrument transformers, specify the low-dielectric-loss variant and confirm tan δ on the batch test report.

Capacitor tissue — very thin, very dense, extremely uniform — appears in CT interlayer insulation and in condenser-type grading structures, where alternating paper and foil layers grade the electric field. Thickness uniformity is everything here: a ±10% thickness variation across a condenser layer becomes a field-stress variation.

Crepe paper handles every position that bends: lead exits, tap connections, irregular joints. Its elongation lets it wrap tight radii without the tears and voids that become PD sites. See our crepe paper technical guide for grades and elongation specs.

CT vs VT: Does the Paper Spec Differ?

Mostly shared, with two practical differences:

  • CTs carry the primary conductor through the core, so the main insulation sits directly around a high-current conductor — thermal cycling is more severe, and thermally upgraded paper is worth considering for the innermost wraps in high-ratio designs.
  • VTs stack many turns of fine wire; interlayer insulation thickness uniformity and smoothness dominate the spec, and any conducting particle risks a turn-to-turn fault in a very finely wound coil.

Both share the same acceptance logic: batch-level test reports for tan δ, dielectric strength, thickness, moisture, and conductivity.

Specification Table for Your RFQ

Parameter Typical requirement (oil-immersed CT/VT) Why
Standard IEC 60554 (grade per position) Comparable quotes, test-method anchor
Thickness / tolerance 0.08 / 0.13 / 0.17 mm; tolerance ±5% or tighter for capacitor tissue Field stress and winding build accuracy
Dielectric loss (tan δ) Low-loss grade; verify per batch Accuracy class and heating
Dielectric strength Per IEC 60554 test method, oil-impregnated Primary electrical rating
Moisture (as delivered) ≤7%; dries below 0.5% in service tan δ stability and aging
Water-extract conductivity ≤10 mS/m Ionic contamination → leakage and PD risk
pH of water extract 6.0–8.5 Long-term cellulose stability
Documentation Mill test report per batch, retained samples Traceability for metering assets

If you are specifying paper for a 220kV-class instrument transformer, the same eight-parameter discipline applies as for power transformers — our 220kV+ insulation paper specification guide includes a copy-ready RFQ spec line you can adapt.

Acceptance and Incoming Inspection

Metering assets justify tighter incoming inspection than power transformers:

  1. Verify tan δ and thickness on the batch MTR against your spec — these are the two parameters that define an instrument-grade paper.
  2. Spot-check thickness uniformity across and along the roll for capacitor-tissue positions.
  3. Moisture check on receipt for paper that will see limited re-drying before impregnation.
  4. Retain reference samples per batch — metering disputes surface years later, and a retained sample settles them.

Frequently Asked Questions

Can I use the same kraft paper for instrument transformers as for power transformers?

The base material is the same cellulose family, but instrument-grade applications add requirements: low tan δ, tighter thickness tolerance, and verified cleanliness. Buy the low-loss grade with batch test data rather than assuming a power-transformer paper qualifies.

What paper is used inside a condenser-type (capacitive grading) CT?

Thin, high-uniformity papers — capacitor tissue or thin cable paper — wound alternately with metallic foil grading layers. Thickness uniformity and freedom from conducting particles are the critical specs.

Does paper choice affect CT accuracy class?

Indirectly but genuinely: dielectric loss contributes phase error, and PD or moisture-driven drift degrades accuracy over time. The paper spec is part of holding accuracy class across the asset life.

What about dry-type or resin-cast instrument transformers?

They replace oil-paper with films, composites, and cast resin systems — a different material family. This guide covers oil-immersed CTs/VTs, where IEC 60554 cellulose papers remain the standard insulation.

Which standard should my RFQ reference?

IEC 60554 for the paper itself (grade, test methods), with the CT/VT product requirements anchored in the IEC 61869 series. Reference both: the first makes paper quotes comparable, the second ties the material to your product’s test obligations.

Working with SIDA

SIDA supplies IEC 60554 cable paper, capacitor-grade thin papers, crepe paper, and pressboard components for instrument transformer manufacturers, with batch mill test reports covering tan δ, thickness, moisture, and conductivity. Send your position list (main insulation / interlayer / leads) and voltage class for a matched grade recommendation and quotation — technical response within 24 hours.

📞 +86-15958243831 | 📧 jessie.feng@sidanm.com | 💬 WhatsApp | 🌐 Contact Us

Related Articles

Conclusion

Instrument transformer paper is not a commodity repackaging of power transformer kraft: low tan δ, thickness uniformity, and verified cleanliness are metering-accuracy requirements, and they must appear in the RFQ and the batch test report. Map the grade to the position — cable paper for main insulation, capacitor tissue for interlayer and condenser structures, crepe for leads — specify against IEC 60554, and inspect on receipt. That is how a CT holds its accuracy class for thirty years.

More Posts

EHV Transformer Insulation: Is Chinese Pressboard Ready for 500kV?

Yes — with qualifications. Chinese G4 high-density pressboard (1.15-1.30 g/cm³, IEC 60641) already insulates the world’s largest EHV fleet, including China’s 1000kV UHV grid. Readiness is proven by type tests, batch CoA and a five-gate qualification process — checklist inside.

Insulation Paper Drying & Moisture Control for Transformer Assembly

Moisture is the biggest accelerator of cellulose aging — target below 0.5% before oil impregnation, dry at 85-105°C under vacuum, verify with Karl Fischer per IEC 60814, store sealed below 65% RH. Method comparison table, five-stage vacuum cycle, and acceptance testing guide inside.

Send Us A Message

Table of Contents

Do You Have Any Questions?

Leave us the insulation materials you are interested in and we will give you the latest catalog and quotation as soon as possible.

Free PDF

Wait — Before You Go, Grab This.

Download our Transformer Insulation Catalog with full specs & standards.

100% Free IEC & NEMA Instant
Download Catalog PDF
No spam. Unsubscribe anytime.