If you are specifying Nomex aramid insulation paper for a motor, compressor, or dry-type transformer, the grade and thickness you write on the drawing matter as much as the material name. “Nomex” is DuPont’s brand for meta-aramid paper; generic aramid papers and aramid-based laminates (NMN, NKN, NHN) follow the same physics at different price points. This guide explains what aramid paper is, decodes the grade system (410, 411, 414, 418, 818), maps the standards that govern it (IEC 60626-2, IEC 60085, UL 1446/746B), and shows where each type actually goes inside a machine.
What Is Nomex / Aramid Insulation Paper?
Aramid paper is made entirely from synthetic meta-aramid polymer in two forms: short fibers (floc) that provide mechanical structure, and microscopic binder particles (fibrids) that fuse the sheet together. The result is a paper that behaves unlike any cellulose material: it does not melt, it maintains useful mechanical and dielectric properties from cryogenic temperatures (−196 °C) up to roughly 400 °C, and it carries a UL 746B relative thermal index of 220 °C for both electrical and mechanical properties — thermal class 220 (C) under IEC 60085.
That thermal headroom is why aramid became the reference material in UL 1446-recognized insulation systems. Where cellulose kraft paper begins degrading above 105 °C and polyester film softens near 130 °C, aramid paper keeps its dielectric strength and dimensional stability at temperatures that would destroy both. In practice, designers reach for aramid when the machine must run hotter, smaller, or longer than cellulose allows.
Grades & Thicknesses: 410, 411, 414, 418/818

The grade number encodes the sheet’s construction, and the construction determines the application. The four that matter in motor and transformer work:
| Grade | Construction | Thickness Range | Key Data (at 10 mil / 0.25 mm) | Typical Use |
|---|---|---|---|---|
| Type 410 | Calendered, dense | 0.05–0.76 mm (10 thicknesses) | 33 kV/mm AC dielectric; 296 N/cm tensile MD; density 0.96 g/cm³ | Slot liners, phase barriers, layer insulation — the default grade |
| Type 411 | Uncalendered, bulky | 0.13–0.58 mm | ~9 kV/mm; density 0.31 g/cm³ | Coil-end filler, cushioning, resin-impregnated structures |
| Type 414 | Calendered for flexibility | 0.09–0.38 mm (5 thicknesses) | 29 kV/mm; high fold endurance | Hand-wound slot cells, wire wrapping |
| Types 418 / 818 | Aramid blended with mica | ~0.08–0.25 mm | Up to 35 kV/mm; superior corona endurance | High-voltage coil wraps where partial discharge sets the life |
The 410 versus 411 decision is the one buyers get wrong most often. They share the polymer and the 220 °C rating, but 410 is roughly three times denser and holds about 3.5 times the voltage per mil. If the part is a barrier holding a defined voltage in a tight slot, specify 410. If the part fills space, cushions, or must absorb varnish and resin, specify 411. Substituting one for the other silently breaks the design in both directions.
A practical purchasing note from recent RFQs we have handled — including a Nigerian buyer specifying 0.24 mm material for 600 V compressor motors: at that voltage class and thickness, the working product is usually not pure aramid paper but an aramid-film laminate, which brings us to the standards.
Standards: IEC 60626-2, UL and the Laminate Codes
IEC 60626-2 governs combined flexible materials — the laminates that bond aramid paper to polymer films. The naming code tells you the construction: the first letter is one face, the middle letter the film core, the last letter the other face. NMN is Nomex–Mylar (polyester film)–Nomex; NKN is Nomex–Kapton (polyimide film)–Nomex; NHN pairs Nomex with polyimide film for class 180+ systems; DMD substitutes polyester fleece for the aramid at lower cost and lower thermal class.
Why laminate at all? The film core contributes dielectric strength and tear resistance; the aramid faces contribute thermal stability and a surface that varnish and resin can wet. An NMN triplex achieves dielectric performance that neither constituent reaches alone — a 12 mil NMN construction is published at 17 kV dielectric breakdown — while remaining far more tear-resistant than paper alone. For Class F (155 °C) and Class H (180 °C) motor systems, NMN and NHN are the standard slot and phase insulation choices under UL 1446 recognized systems.
When evaluating any aramid paper or laminate, three numbers on the data sheet decide fitness: AC dielectric strength (kV/mm, per ASTM D149), thermal class confirmation (UL 746B RTI or IEC 60216 aging data), and — for anything above a few kilovolts — partial discharge behavior. DuPont’s own guidance caps continuous operating stress at about 1.6 kV/mm in transformers to keep partial discharge at bay; treat any supplier data sheet quoting only short-time breakdown values with appropriate caution.
One procurement red flag deserves emphasis: thickness tolerance. Low-voltage slot work assumes the nominal thickness within ±10%; a roll measuring thin across the middle silently reduces your dielectric margin on every liner cut from it. Specify the tolerance on the purchase order, and verify incoming rolls with a micrometer at several points across the web — a five-minute check that has caught more than one out-of-spec shipment.
Aramid Board and 220 °C Structural Parts
Beyond paper, the same polymer family is pressed into rigid aramid board — dense sheets that hold mechanical properties at temperatures where cellulose pressboard (class 105–120) and even epoxy glass (class 155–180) are beyond their ratings. A 100% aramid board carries the class 220 rating into structural roles: spacers, support blocks, and end laminations in compact high-temperature transformer designs, traction motors, and aerospace applications where the insulation must double as a load path at 200 °C-plus.
The trade-off is cost and machining. Aramid board runs several times the price of cellulose pressboard per kilogram and demands sharp tooling and controlled feed rates to avoid fuzzy edges. Specify it only where the thermal design genuinely requires class 220 structure — everywhere else, cellulose or epoxy glass does the job for a fraction of the cost.
A useful rule of thumb for the material ladder: cellulose pressboard covers class 105–120 at the lowest cost per part; epoxy glass laminates reach class 155–180 with superior mechanical strength; aramid board occupies class 220 where nothing else survives. Moving up one rung typically multiplies material cost by three to five, so the correct engineering question is never “what is the best material” but “what is the lowest class that survives my hot-spot temperature with margin.”
Motor & Compressor Applications

Inside a motor or hermetic compressor, aramid-based insulation appears in four positions:
- Slot liners: the barrier between copper and stator iron — typically Type 410 or NMN, in thicknesses matched to voltage class (0.13–0.25 mm covers most low-voltage machines up to 600 V).
- Phase insulation: separating winding groups at the end turns — NMN for tear resistance during forming, or 411 where bulk filling matters.
- Slot wedges / top sticks: closing the slot — thicker 410 (0.25–0.38 mm) for stiffness.
- Lead and jumper wraps: aramid tapes and sleeving where flexibility and heat resistance meet; see our aramid paper tapes for these positions.
Compressors add one more demand: refrigerant and oil compatibility. Aramid papers perform well in common refrigerant environments, which is why they are standard in hermetic compressor motors alongside NMN laminates. For high-temperature systems above class 180, NHN constructions with polyimide film cores take over. These flexible laminates sit in category 8 of our 17-category insulation checklist, alongside the DMD options for lower thermal classes.
Frequently Asked Questions
Is generic aramid paper equivalent to Nomex?
Chemically, yes — both are meta-aramid papers with 220 °C ratings. The differences are consistency and documentation: DuPont grades carry decades of UL 1446 system data, which matters when your insulation system itself is UL-recognized. For new builds under an existing recognized system, specify the named grade. For cost-sensitive designs outside UL scope, qualified generic aramid papers deliver the same thermal class at lower cost — verify with IEC 60216 aging data from your supplier.
How do I choose between NMN and pure Nomex 410 for slot insulation?
Compare three numbers: required dielectric withstand, tear exposure during winding insertion, and cost. NMN wins on tear resistance and cost per dielectric; 410 wins on thermal purity (no polyester core) and system heritage. For Class F machines at 400–600 V, 0.24 mm NMN is the industry workhorse. For Class H or traction duty, move to 410 or NHN.
What should I check when qualifying an aramid paper supplier?
Ask for the thermal aging data supporting the class claim (IEC 60216 or UL 746B), dielectric strength per ASTM D149 on the exact thickness you buy, and batch test reports with measured values. Our supplier qualification checklist covers the full verification process.
What aramid products does SIDA supply?
We supply aramid paper tapes, NMN and NHN flexible laminates, and DMD composites in rolls, sheets, or slit-to-width formats, with batch test reports and samples for qualification. Send your grade, thickness, and width requirements by email or WhatsApp — we quote within 24 hours and ship trial quantities from a single roll. Contact us to start.
Summary
Nomex aramid insulation paper earns its premium through thermal class 220 performance that cellulose and polyester cannot touch. Specify Type 410 for barriers under voltage, 411 for bulk and impregnation, 414 for hand-wound flexibility, and 418/818 where partial discharge rules. For most Class F motor slots, NMN laminate per IEC 60626-2 is the economical workhorse; NHN covers class 180+. Match the grade to the position in the machine, anchor the claim to thermal aging data, and the aramid premium pays for itself in machine life.
📞 +86-15958243831 | 📧 jessie.feng@sidanm.com | 💬 WhatsApp | 🌐 Contact Us
References
- DuPont — Nomex® Paper Type 410 Technical Data Sheet (electrical properties by thickness): https://www.dupont.com
- IEC 60626-2 — Combined flexible materials for electrical insulation: https://webstore.iec.ch
- IEC 60085 — Electrical insulation, thermal evaluation and designation: https://webstore.iec.ch
- UL 746B / UL 1446 — Polymeric materials long-term evaluations and insulation systems: https://www.ul.com